The Alcor Commercial &Industrial Liquid-Cooled Energy Storage Cabinet is astandardized outdoorenclosure that integrates long-life battery cells,innovative battery management system(BMS)controlstrategies,high-performance power conversion systems(PCS),intelligent temperature controlsystems,and active fre protection control systems. Designed with completely separate compartments forelectrical components and battery modules,it signifcantlyenhances thermalmanagement reliability and fre safety.Suitable forawide range of applications including peak shaving,renewable energy integration,dynamic capacity expansion,andlow-voltage grid regulation.

DataSheet
Parameters

Model

TESS-125-262-LTE

AC (Grid tied)

Rated Power

125kW

Rated Voltage

40OV

Rated Current

180A

AC System Wiring Type

3L/N/PE

Voltage Range

40OVac(-15%~+10%)

Rated Frequency

50Hz/6OHz

THDI

<3%(Rated   power)

Power Factor

>0.99

Power Factor Range

±1

Overload Capability

110%overload(10 min),120%overload(1min)

AC(Off-grid)

Rated Power

125kW

Rated Voltage

400V

Rated Current

180A

Rated Frequency

50/60Hz

THDU

<3%(Linear load)

DC(Battery)

Cell Type

LFP3.2V/315Ah

Configuration

260SIP

Charge/Discharge Rate

≤0.5

Rated Battery Voltage

832V

Battery Voltage Range

702V~936VDC

Basic Parameters

Noise

<75dB

Protection Rating

IP54

Corrosion Protection

C3

Operating Temperature

-20~55℃

Firefighting Agent

Aerosol

Cooling Method

Module liquid cooling+PCSair cooling

Relative Humidity

Aerosol0~95%,without condensation

Max.Altitude

≤4000m(Deratedabove 2000m)

Dimensions(W×D×H)

960×1400×2350mm

Weight

2500kg

Certifications

Battery:IEC61000-6-2/4,IEC62477-1,IEC62619,U1973,UL9540A,UN38.3
PCS:IEC62477-1,EN61000-6-2/4,EN50549-1/10

Communication

Display

Touch Screen

Communicationlnterface

IRS485+1WAN+1LAN

Communication Protocol

Modbus TCP/RTU

* Note:PCSpoweroptionsinclude100kW,110kW,and125kW.
Maximumbattery powershall not exceed0.5P.